QUARTAS Single Detector
Very Early Warning Aspirating Smoke Detector
QUARTAS-500s
Single Pipe
Aspirating Smoke Detector
Max. no. of Sampling Holes | |
- Class A | 40 |
- Class B | 60 |
- Class C | 60 |
Max. Sampling Pipe Length | |
- Single Pipe | 100m |
- Two Brached Pipe | 2 x 80m |
- Four Branced Pipe | 4 x 60m |
QUARTAS-2000s
Four Pipes Scanning
Aspirating Smoke Detector
Max. no. of Sampling Holes | |
- Class A | 40 |
- Class B | 60 |
- Class C | 100 |
Max. Sampling Pipe Length | |
- Single Pipe | 4 x 100m |
- Two Brached Pipe | 4 x 2 x 80m |
QUARTAS-2000s Pipe Scan
Taking advantage of the four individual aspirators in the QUARTAS-2000s, in case of fire it can turn on and off each aspirator in sequence to “identify” the pipe having the most smoke.
Read More
Read More
BLUE LED DETECTION
► High Power Blue LED Light Source
► Wide Angle Nephelometer Mass Detection
► Maximum Detection Sensitivity 0.001%/m
► Maximum Alarm Sensitivity 0.005%/m
► Wide Angle Nephelometer Mass Detection
► Maximum Detection Sensitivity 0.001%/m
► Maximum Alarm Sensitivity 0.005%/m
MULTIPLE FUNCTION DISPLAY/ PROGRAMMER
►Display
- Smoke, Flow, Address, Event/Error Code
- 20 Segments Smoke Bargraph
- Alarm and Fault Indicators
► Control
- Reset/Isolate/Silence/Test Buttons
► Programmer
QUARTAS-500s
Tyipical Applications
- Internet Data Center
- Computer Room
- Telecom Room
- Control Room
- Electrical Room
- Air Conditioning Facilities
- Cleanrooms
- Railway Coach
- ESS Energy Storage System
QUARTAS-2000s
Typical Applications
- Warehouse/High Bay Wareshouse
- Distribution Center
- Airport
- Transportation Station
- Mueseum/Gallary
- Cleanrooms
- Electrical Room
ASD Specifications |
|||||
Items | QUARTAS-500s | QUARTAS-2000s | FANFARE-2000 | FANFARE-4000 | |
Detection Light Source | High Power Blue LED | ||||
Detection Principle | Forward Light Scattering | ||||
Detection Sensitivity Range | 0.001~25 % obs/m | ||||
Alarm Sensitivity Range | 0.005~20 % obs/m | ||||
Alarm Level | 4 Stages (Alert, Action, Fire-1, Fire-2) | ||||
Alarm and Fault Time Delay | 0~60 (Sec.) | ||||
Sensitivity Switch | 2 (0.1~10) | ||||
Flow Learning | 6 Flow Sensitivity Learning Mode | ||||
Environment Smoke Learning | 15 / 60 / 120 / 240 / 480 minutes (Non-Stop) | ||||
Fan Speed | 10 Steps Adjustable | ||||
High Sensitivity Smoke Chamber | 1 | 1 | 4 | 8 | |
High Efficiency Aspirator | 1 | 4 | 4 | 8 | |
Flow Sensor | 1 | 4 | 4 | 8 | |
Air Sample Inlet Port | 1 | 4 | 4 | 8 | |
Air Sample Exhaust Port | 1 | 1 | 4 | 8 | |
Two Stages Filter | 1 | 1 | 4 | 8 | |
Local Display / Programmer | Numerical Value Display | Smoke Level / Flow Level / Address / Event Code and Aux. Sensor Level (if fitted) | |||
Bargraph | 20 seg. Bargraph x 1 | 20 seg. Bargraph x 4 | 20 seg. Bargraph x 8 | ||
Indicator LED | 10 (OK / Isolate / Alert / Action / Fire 1 / Fire 2 / Det'n / Flow / System /Aux.) | 6 (OK / Ioslate / Det'n / Flow / System / Aux.) + 6x4 (Fault/Alert/Action/Fire 1/Fire 2) | 6 (OK / Ioslate / Det'n / Flow / System / Aux.) + 6x8 (Fault/Alert/Action/Fire 1/Fire 2) | ||
Control Buttons | 6 (Reset / Silence / Isolate / Test / Left / Right) |
8 (Reset / Silence / Isolate / Test / Left / Right / Up / Down) |
|||
Beeper | Yes | ||||
Programmer | LED Type | LCD Type | |||
Remote Display / Programmer | Numerical Value Display | NA | |||
Bargraph | |||||
Indicater LED | |||||
Control Buttons | |||||
Beeper | |||||
Programmer | |||||
RS485 Network | Yes | ||||
RS485 Repeater | Yes (Extend 1,200m) | ||||
General Purpose Input (GPI) | 4 (Configurable) | 8 (Configurable) | |||
Relay Output | 7 (Configurable) | ||||
Zone Relay | NA | 16 relays (optional) | 16 relays | 32 relays | |
Auxilliary Sensors | Optional (Temp./Humidity and Gas Sensors) | ||||
Event and Data Logs | 180,000 (items) | ||||
Sampling Pipe Length | Total Pipe Length | 240m | 640m | 640m | 1280m |
Single Pipe Length | Single Pipe 100m, Branched Pipe 160m | ||||
No. of Sampling Holes | Class A / VEWFD | 30 Holes | 40 Holes | 40x4=160 Holes | 40x8=320 Holes |
Class B / EWFD | 60 Holes | 60 Holes | 60x4=240 Holes | 60x8=480 Holes | |
Class C / SFD | 60 Holes | 100 Holes | 400 Holes | 800 Holes | |
Maximum Coverage | 500m²;Max 1,000m² | 2,000m² | 2,000m² | 4,000m² | |
Sampling Pipe Specification | OD:Φ25mm/ID:Φ21mm | ||||
Capiliary Tube Specification | OD:Φ8/ID:Φ5 | ||||
Operating Voltage | 24Vdc ±6 | ||||
Operating Current | 350mA | 730mA | 1.13A | 2A | |
Ambient Temperature | 0~50°C | ||||
Max. Temperature under Sun | 70°C | ||||
Sampling Air Temperature | -30~60°C | ||||
Operation Humidity | 0~95%RH, Non Condensing | ||||
Dimensions (W x H xD) | 215 × 202 × 85mm | 415 × 259 × 108mm | 426 × 291 × 130mm | 670 × 291 × 130mm | |
Weight | 1.5kg | 5.2kg | 7.5kg | 12.1kg |